CISA: Siemens SIMATIC, .NET S7 Library Hit by Critical Flaws
U.S. cybersecurity agency flags path-traversal and authentication-bypass vulnerabilities in widely deployed German industrial software.
Authenticity Score: 88/100 across 1 source(s). First reported: 2026-11-17T12:00:00Z. Updated: 2026-11-21T18:21:04Z.
CISA published two advisories on 17 November 2026 disclosing critical vulnerabilities in Siemens industrial-control products. One affects the .NET Client Library for SIMATIC S7 Webserver API, allowing path traversal and information disclosure; the other exposes multiple SIMATIC product lines to session hijacking and arbitrary code execution. Siemens has released patches for the .NET library and is preparing fixes for the broader SIMATIC suite.
Verified Key Facts
- CISA issued two official advisories on 17 November 2026 for Siemens industrial software vulnerabilities
- CVE-2026-85114 and CVE-2026-85115 affect .NET Client Library for SIMATIC S7 Webserver API versions <3.3.61/<3.3.62; patches are available
- CVE-2026-58114 affects 12+ SIMATIC product lines including WinCC and Process Historian; patches are in preparation
- Authentication bypass in SIMATIC products allows on-path session hijacking and arbitrary code execution with victim privileges
- Siemens headquarters is in Germany; affected systems are deployed worldwide in critical manufacturing sectors
The U.S. Cybersecurity and Infrastructure Security Agency (CISA) issued two coordinated advisories on 17 November 2026 covering vulnerabilities in Siemens industrial automation software. Both advisories are classified as trust-tier-1 official government sources.
The first advisory (CVE-2026-85114, CVE-2026-85115) concerns the Siemens .NET Client Library for SIMATIC S7 Webserver API, versions below 3.3.61 and 3.3.62. CISA confirmed that improper validation of filenames during ticket downloads permits path-traversal attacks and that error messages may leak sensitive information. Siemens has released updated versions and urges immediate patching. The affected library is deployed worldwide in critical manufacturing sectors.
The second advisory (CVE-2026-58114) discloses an authentication-bypass vulnerability across numerous SIMATIC product lines, including SIMATIC BATCH V9.1, SIMATIC Information Server 2020/2022, SIMATIC PCS 7 V9.1, SIMATIC Process Historian 2020/2022, and multiple versions of SIMATIC WinCC (V7.5 through V8.1) and WinCC Runtime Professional (V17 through V21). CISA confirmed that an on-path attacker could hijack a legitimate user's session and execute arbitrary code with victim privileges. Siemens is preparing fixes and has published interim mitigations for products where patches are not yet available.
Both vulnerabilities carry significant implications for operational-technology security given the global deployment of Siemens SIMATIC systems in energy, manufacturing, and process industries.
Corroborating Sources
- CISA Cybersecurity Advisories